Fire Control Panel FS 5200
- DESCRIPTION
FS5200 is already certified by EVPU!!!
FIRE ALARM LINES
– Maximum number of fire detectors in a line: 32
– Connecting line: two-wire
– Maximum resistance of a line: 100Ω
CONTROLLABLE OUTPUTS
– Type: Potential
– Electrical characteristics: (24±5)V/500 mA
RELAY OUTPUTS FOR FAULT CONDITIONS
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC; 3 A/30 V DC
RELAY OUTPUTS FOR FAULT CONDITIONS
– Type: potential free, switching
– Electrical characteristics: 3 A/125 V AC; 3 A/30 V DC
INDICATIONS OF REGISTERED EVENTS
– Light indication: LEDs
– Text messages: LCD display – 4 lines, 20 symbols, Latin/Cyrillic characters, backlit
– Sound: Built-in sounder
ACCESS LEVELS TO CONTROL FUNCTIONS: 4 (in compliance with EN 54/2)
POWER SUPPLY
– Voltage: 220/230 V
– Frequency: 50 Hz
BACKUP BATTERIES: 2x12V / 12 Ah
OPERATION IN DUTY MODE UPON INTERRUPTED MAINS SUPPLY
– Minimum configuration: 80 h
– Maximum configuration 30 h
CONSUMPTION ON BACKUP BATTERIES SUPPLY IN DUTY MODE AT 24 V
– Minimum configuration: <155 mA
– Maximum configuration: <400 mA
POWER SUPPLY TO EXTERNAL DEVICES
– Voltage: (24±5)V
– Maximum current value (current of controllable outputs included): 1,5 A
WEIGHT (BACKUP BATTERIES NOT INCLUDED): 6,6 kg
DIMENSIONS: 450 x 355 x 115mm
OPERATING TEMPERATURE: -5 oC to +40 oC
RELATIVE HUMIDITY: to 93 %
DEGREE OF PROTECTION: IP 40